freezemaster™ Antifreeze Blog
In-depth antifreeze and fire safety advice and insights from the experts behind the freeze protection technology like no other.
Codes, Standards & Approvals | FAQs
Most antifreeze sprinkler systems now incorporate listed antifreeze, as it has proven to keep those critical systems safely functioning at optimal levels.
Share
It’s nearly winter again, and prepping for the cold typically includes testing antifreeze in wet fire sprinkler systems. The typical process for inspecting wet fire sprinkler systems involves:
Share
FAQs | Installation | Temperature | fire sprinkler systems
Because the primary purpose of antifreeze is to protect sprinkler systems from cold, contractors tend to only consider the minimum use temperature when selecting a listed antifreeze.
Share
Codes, Standards & Approvals | FAQs
NFPA standards require all antifreeze fire sprinkler systems to switch to a listed antifreeze by September 30, 2022. These standards help ensure that an antifreeze system performs reliably in a fire and saves more lives, rather than contributing to fire as unlisted fluids can.
Share
Codes, Standards & Approvals | FAQs | Installation
When installing listed antifreeze, the manufacturer’s installation guide is the final word. But talking with installers who have already started switching their clients to a listed product has revealed three installation tips that you won’t find in the official installation guide.
Share
A UL-listed, factory-premixed antifreeze – like freezemaster™ antifreeze – will soon be the new normal for sprinkler systems needing seasonal freeze protection. This new normal requires different installation and maintenance than building owners and ITM contractors are used to with traditional antifreezes. Not taking these differences into account significantly shortens the life of listed antifreeze.
Share
Before July 2021, a listed antifreeze approved for use in Ordinary Hazard 1 & 2 sprinkler systems larger than 40 gallons did not exist, even though many of these buildings require a system with significantly more antifreeze. This limitation made it difficult and expensive for antifreeze-based fire sprinkler systems in larger applications to maintain compliance with NFPA requirements.
Share
Codes, Standards & Approvals | FAQs | Installation Guide | Listings and Innovations | fire sprinkler systems
Size matters!
Share
Codes, Standards & Approvals | FAQs
Planning for freezing temperatures during the sweltering summer might not be the first thing on anyone’s to-do list in the fire sector. But in the case of sprinkler system freeze protection, 2021 is the year it should be. Advance planning, insights from the field and a broad perspective on where winterizing is needed will be useful to prepare for safe, effective freeze protection in sprinklered applications this winter and next.
Share
Fire sprinkler systems can be prone to a specific category of corrosion plaguing the industry known as microbiologically influenced corrosion, or MIC. According to the FM Global report “Corrosion and Corrosion Mitigation in Fire Protection Systems,” MIC is responsible for 10-30% of corrosion in all piping systems in the U.S.
Share
During the years when there were no listed antifreezes to protect fire sprinklers from freezing in severely cold weather, dry pipe systems were often chosen to fill the void after NPFA put into place new regulations requiring listed antifreezes for new systems. The most common applications affected by this included attics, unheated warehouses, commercial freezers, overhead canopies, loading docks and parking garages. Now that listed antifreezes are commercially available, however, it’s worth evaluating experiences from the field where dry system use increased in situations where it might not have been best suited. While these systems can be the right solution in some scenarios, they can have significant drawbacks in others.
Share
Codes, Standards & Approvals | Flammability
Fire sprinkler contractors who have an inspection, testing and maintenance (ITM) business are looking at new protocols for water-based fire protection systems.
Share
Sprinkler pipes must be safeguarded when temperatures cannot reliably remain at or above 40ºF (4ºC) ambient temperature. New and existing sprinkler systems in Residential, Light Hazard, Ordinary Hazard and Storage applications can be protected against severe cold with freezemaster™ antifreeze, a new UL-listed, factory premixed freeze protection technology.
Share
Building owners need assurance that their fire protection systems are functioning to lower the risk of an uncontrolled fire loss. Fire suppression system contractors need confidence that the systems they install will not freeze and will provide the best corrosion protection on the market.
Share
NFPA fire sprinkler standards require new antifreeze systems to use an agency-listed antifreeze. And these same standards require that existing systems use an agency-listed antifreeze by September 30, 2022. These standards are intended to ensure an antifreeze system is designed and installed using the safest and most reliable practices in the industry.
Share
Have you ever wondered why antifreeze in water-based fire sprinkler systems requires yearly testing before the onset of freezing weather? Simply put, testing ensures that the antifreeze maintains its proper concentration and freeze point. It must always remain in a liquid state and address the life safety issues associated with antifreeze use. To ensure this, the concentration of antifreeze solution should always be no more than the least amount necessary for the anticipated minimum temperature. In the event of leaks, pressure surges or temperature changes to the system, antifreeze can flow out of the system or water can flow into the system, leading to changes in the freeze temperature and antifreeze concentrations. If concentration conditions deviate from allowable tolerances, as illustrated by the chart below for freezemaster™ antifreeze, the fluid must be replaced. Because freezemaster™ antifreeze is a UL-listed, safe to use, factory premixed antifreeze, the percent concentration by volume would always be 100 percent.
Share
Many are not aware that the National Fire Protection Association (NFPA) fire sprinkler standards require new antifreeze systems to use an agency-listed antifreeze. And these same standards require that existing systems use an agency-listed antifreeze by September 30, 2022. In fact, when safety concerns led to these NFPA updates, no listed product was available.
Share
Codes, Standards & Approvals | FAQs
As you select an antifreeze for your fire sprinkler system, it is important that you consider these questions: Does it meet the rigorous technical challenges of becoming listed as required by NFPA? Is it listed and approved for use with the application and the size of the system? Will it protect the system against damage from exposure to the severe cold? How does it contribute to the prevention of corrosion and microbiologically influenced corrosion (MIC)? In this blog post, I address why the answers to these questions are so critical, and the advantage freezemaster™ antifreeze offers for fire sprinkler systems in Residential, Light Hazard, Ordinary Hazard and Storage applications.
Share
The 2014 edition of NFPA 25, the standard for the inspection, testing and maintenance of water-based fire protection systems, was written to specifically include emergency changes regarding the use of antifreeze. Those changes were based on events in which activated sprinkler systems, fortified with antifreeze, actually intensified blazes rather than extinguished them. This was likely due to onsite errors in mixing the solutions that introduced excessive amounts of the active ingredients glycerin and propylene glycol, both of which increase flammability when present in high concentrations.
Share
UL 2901 was established in December 2013, outlining certification requirements for antifreeze solutions for wet pipe fire sprinkler systems. To meet the UL 2901 requirements, antifreeze products must prove corrosion resistance (important for metal-based fire sprinkler systems), fire performance (i.e., flammability), hydraulic characteristics, human health and environmental impact, and meet marking and installation specifications.
Share
When a fire sprinkler system activated as designed in 2009 to suppress a cooking fire – and instead intensified the blaze, killing one and injuring four – the use of antifreeze in sprinkler systems changed forever. The sprinkler system contained antifreeze that had been mixed improperly before application. A high concentration of the antifreeze agent caused the flames to virtually explode when the sprinkler system activated.
Share
Codes, Standards & Approvals | Temperature
NFPA 25 is the standard for the inspection, testing and maintenance of water-based fire protection systems. Once adopted by local code bodies, authorities having jurisdiction (AHJs) require strict adherence to NFPA 25 – and frankly, there is no reason not to design, repair or maintain a system to the standard.
Share